tel:
+86 18927380683email:
CNjhy@jhycable.com(UL & RoHS) XHH 90℃ 600V Copper core XLPE insulated single core cable
For exposed wiring and conduits in wet and dry locations (except cable bridges). Suitable for outdoor use and wiring exposed to the weather
-40°C cold bending and -40°C cold shock; low smoke and zero halogen
RoHS ; CSA C22.2 No.38; UL44
Conductor material: tinned copper or bare copper stranded wire
Conductor Type: UL44 compliant. Conforms to ASTM B3, B8 and B33 or NMX-J-008-ANCE requirements
Core Insulation: XLPE
Core marking: Optional
Rated voltage: 600V
Test voltages are as follows:
|
Conductor Specifications |
1min testing voltage,kV |
||
|
mm² |
AWG/kcmil |
600V |
1000V/2000V |
|
2.08-5.26 |
14-10AWG |
3.0V |
6.0V |
|
8.37-33.6 |
8-2AWG |
3.5V |
7.5V |
|
42.4-107 |
1-4/0 |
4.0V |
9.0V |
|
107-253 |
4/0-500kcmil |
5.0V |
10.0V |
|
253-507 |
500-1000kcmil |
6.0V |
11.0V |
|
507-1010 |
1000-2000kcmil |
7.0V |
13.5V |
Conductor resistance: UL1581 ASTM Class C
Minimum bending radius fixed laying value: 15x d
Minimum bending radius mobile laying value: 15x d
Operating temperature fixed small value / large value: -40℃/90℃
Flame retardant grade: self-extinguishing and flame retardant in accordance with UL1581 VW-1;CSA C22.2 No.2556-15 FT1, FT2;IEC 60332-1-2
Certification: UL