Power, control and connection cables for drive systems with frequency converter technology for fixed laying and random movement without tensile stress and without defined cable routing. For use in dry, damp and humid rooms. For outdoor use (black colour), but not to be laid underground.
Highly resistant to acids, alkalis and specific types of oils
Black version with UV-resistant outer sheath.
EMC-compatible shielding for trouble-free operation of the inverter.
RoHS compliant
Complies with the 2014/35/EU guideline ("Low Voltage Directive") CE
Special versions, other sizes, cross-sections, core and sheath colours on request.
Conductor material: Bare copper stranded wire
Conductor class: according to IEC 60228 Division 5
Core insulation: PE
Stranding: Stranded in layers
Shield: polyester tape, aluminium foil 100% covered, tinned copper shielding
Sheath: PVC
Sheath Colour:Transparent
Rated voltage:Uo/U:0.6/1KV
Test Voltage:Uo/U: 4KV
Minimum bending radius fixed: <12 mm: 5xd; <20 mm: 7.5xd; >20 mm : 10 xd
Minimum bending radius moving: <12 mm: 10xd; <20 mm: 15 xd; >20 mm: 20 xd
Temperature fixed min/max: -40°C/+80°C
Moving temperature minima/majima: -5°C/+70°C
Conductor temperature: +70°C in operation; +160°C in short circuit
Flammability behaviour: self-extinguishing and flame retardant acc. to IEC 60332-1